The ISOWIND panel range is an insulated panel which can be used for temperature control and food & hygiene safe applications within an internal temperature range between +40¢XC and -40¢XC. Applications include food processing, chill/cold store and deep freeze, and clean room environments.


Insulation Panel - Heat Transmission

Thermal Conductivity (£f) 0.023 W/mk

Heat Transmission : W/sq. m

Panel Thickness(mm)

60

100

130

150

Thermal Transmittance W/sq.m K

0.25

0.20

0.16

0.13

Temp. Difference

10¢XC

2.5

2.00

1.60

1.30

15¢XC

3.75

3.00

2.40

1.95

20¢XC

5.00

4.00

3.20

2.60

25¢XC

6.25

5.00

4.00

3.25

30¢XC

7.50

6.00

4.80

3.90

35¢XC

8.75

7.00

5.60

4.55

40¢XC

10.00

8.00

6.40

5.20

45¢XC

11.25

9.00

7.20

5.85

50¢XC

12.50

10.00

8.00

6.50

The recommended minimum insulation value for coldstores is 10W/m2 heat gain.
To calculate the above use : D = £f x #t /Q

Where:
D = thickness of insulation (mm)
£f = lambda value of insulation (W/mK)
#t = temperature difference between internal and external face.
Q = heat flow = 10(W/sq. m)